SURGE ARRESTER: JENSEN 8264/2
2-POLE, 350 V

(document no 9236)

Productindex | Home


Mechanical characteristics:



Electrical characteristics:

  MIN TYP MAX Note
DC Breakdown voltage, (V) 280 350 420 (Un +/- 20%)
Glow voltage (V)   186   At 10 mA
Dynamic breakdown voltage (V)   600 1000 At 2kV/µs ramp
Insulation (ohm) 1E10     At 100V, 50% rh
Insulation (ohm) 1E8     At 100V, 95% rh
Capacitance (pF)   2    
Load tests:
Surge   5 applications of 10 kA surges with shape 8/20µs.
Surge   50 applications of 1 kA surges with shape 8/20µs.
Surge   50 applications of 100 A surges with shape 10/1000µs.
AC       20 applications of 20A (rms, Ac 50Hz). Each application cosists of two
            0.5s pulses separated by a 0.4s pause. 120s interval between applications.

Environmental characteristics:

All characteristics listed below refers to, and fulfills the corresponding paragraphs in
ITU-T K.12 05/95

Robustness of terminations    7.1
Solderability    7.2
Resistance to soldering heat    7.3
Vibration    7.4
Damp heat cyclic    7.5
Sealing    7.6
Low temperature    7.7




Copyright © 2002 JENSEN Devices AB